What AD B asks of an escape window
Approved Document B Volume 1 is the fire safety guidance for dwellings in England, in its 2019 edition incorporating 2020, 2022, 2025 and 2026 amendments. Para 2.2 deals with upper storeys a maximum of 4.5 m above ground level. A habitable room there needs an emergency escape window or external door, as described in para 2.10, or direct access to a protected stairway.
Para 2.10 describes the escape window in three limits:
- "A minimum area of 0.33m2."
- "A minimum height of 450mm and a minimum width of 450mm", where the route through the window may be at an angle rather than straight through.
- "The bottom of the openable area is a maximum of 1100mm above the floor."
Para 2.10 adds that people escaping should reach a place free from danger from fire, and that the window should stay open without being held. The limits apply to the openable part of the window and not to the frame, so the open sash is what is measured. A window that looks large from outside can fall short once the sash has opened and the frame has taken its share.
The same edition says "The 2029 amendments take effect on 2 September 2029 for use in England", so the text above is the one in force at the time of writing.
Why 4.5 m is the line
An escape window is a way out for a storey up to 4.5 m above the ground. Above that height the document asks for something else. Para 2.5 covers a dwellinghouse with one storey more than 4.5 m above ground level, and it gives two options.
- A protected stairway, which is a stair separated by fire resisting construction, minimum REI 30, at all storeys.
- An alternative escape route, where a top storey is separated from the lower storeys by fire resisting construction, minimum REI 30, and has an alternative escape route leading to its own final exit.
Para 2.21 applies where a loft conversion creates a new storey above 4.5 m, and says the full extent of the escape route should be addressed. Para 2.23 gives a different option for open-plan layouts, which is sprinkler protection to the open-plan areas, together with a fire resisting partition and door to the ground storey and separated cooking.
So a storey above 4.5 m has a choice of routes and none of them is a roof window alone. A window can still be fitted to light that storey, and it is then judged as a window and not as the way out.
Measuring a roof window against the limits
Check these figures before the window is ordered and not after it is fitted. For a loft room that depends on a roof window for its way out, we ask for the following in writing.
| Check | AD B limit |
|---|---|
| Clear area of the opening | At least 0.33m2 |
| Clear height and width | 450mm each, at least |
| Lowest point of the opening | 1100mm or less above the floor |
The last row is the one that catches roof windows. A window set high in a slope can have its openable area start above 1100mm from the floor, because the sill sits where the slope puts it. The position on the slope therefore matters as much as the size of the window.
The maker's data for each model gives its clear opening, and that is the figure to compare with the table. A like-for-like swap into an opening that already works should be checked again, because a new model can have a different opening from the one it replaces.
Who confirms it, and the written price
Building control is carried out by the council's building control team or by a registered building control approver. Put the question of the loft room's way out to the body for your address, and do it before the window is ordered. Where the house is in Havant, we take the question to your building control body ourselves, ahead of the booking.
Have these to hand when you ask:
- The height of the storey above ground, measured outside.
- The maker's clear opening for the model you are considering.
- The height of the lowest point of the openable area above the finished floor.
The energy figure on a roof window is a separate check, and our guide to roof window energy rules sets it out. Our answer on building regulations for a new roof window covers the wider route.