What a cold roof is and why it needs air
A cold roof is a pitched roof where the insulation is laid along the ceiling, leaving the loft above cold. Warm, damp air from the rooms below can still drift up into that space, and where it meets the cold underside of the roof it can turn to condensation on the timbers and the sheet.
Ventilation is how a cold roof clears that moisture. Air enters at the eaves, which are the bottom edge of the slope, passes through the loft and leaves higher up. BSI lists BS 5250:2021, the moisture-management standard behind this, as current and under review.
The gap at the eaves is a design feature, and it is easy to lose by accident. Paint can fill it, new soffit boards can cover it, and insulation pushed into the corner of the loft from inside can block it. Each of these closes the air route without changing how the roof looks from outside.
The first job at a survey is to find out what sort of roof you have, because the answer changes what is needed.
The published figures for an HR underlay
HR means high resistance. Marley says vapour does not pass through an HR underlay, so any moisture in the loft needs ventilation at the eaves to carry it away. For a cold roof, Marley gives the following.
| Roof pitch | Ventilation along the length of the eaves |
|---|---|
| 15 degrees or less | 25mm |
| More than 15 degrees | 10mm |
The units matter, and so does the wording. Marley frames the figures as ventilation for a cold roof with an HR underlay, so they do not describe a warm roof, where the insulation sits at the rafters.
The units matter. Both figures are a continuous gap along the length of the eaves, in millimetres, and they are Marley's guidance for its own system, so the data sheet for your product is the document to read. We check the sheet for the underlay actually on the roof before saying what the eaves need.
Do not treat these numbers as a repair specification for a house nobody has surveyed. They are published figures for one case, and a roof that is shaded, extended, or insulated in some other way can need something else entirely.
Air-permeable underlay and the 3 mm case
The other kind of underlay lets air and vapour pass through it. For that kind, over a well-sealed ceiling, Marley says "fortuitous ventilation at the eaves via normal eaves construction (3mm) is all that is required, provided the requirements of UKAS Third Party certification are fully met."
Two conditions in that sentence do the work. The ceiling has to be well sealed, so little moisture reaches the loft in the first place, and the certification has to be met in full, which concerns the product and how it is installed. Without both, the 3mm case does not apply.
Fortuitous is a technical word for ventilation that arrives through the ordinary gaps in the eaves construction, not through a purpose-made vent. Nobody has to cut a new opening, but the gaps that exist must stay open, and that is worth checking before any insulation goes in.
This is why one answer cannot cover every house. The ventilation rests on a pair of choices made when the roof was covered: which underlay, and how well the ceiling beneath it is sealed.
Checking the eaves from the loft
With a torch at the hatch, and standing on the ladder and never on the bare ceiling, you can read some of this for yourself.
- look into the eaves corner for insulation pushed hard against the roof
- check for daylight or moving air where the roof meets the wall
- look for dark spotting, damp or mould on the rafters and the sheet
- see whether the soffit outside has vents, and whether paint covers them
None of these tells you which underlay is on the roof. That takes a closer look, which we make at survey, raising tiles where we need to see the sheet. We then explain what the loft needs and why.
Where the eaves have been blocked, the fix is to open the air path again. Where the underlay is the wrong type for the ventilation, that can be corrected when the roof is re-covered. The work and its single written price follow the survey.
Our guide to tracing and fixing pitched roof leaks covers the signs to look for, and our pitched roofing page sets out the wider work.